WARNING
Electric shock due to unconnected cable shield
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
As a minimum, connect cable shields and the conductors of power cables that are not used
(e.g. brake cores) at one end at the grounded housing potential.
WARNING
Arcing when a plug connection is opened during operation
Opening a plug connection when a system is in operation can result in arcing that may cause
serious injury or death.
Only open plug connections when the equipment is in a voltage-free state, unless it has
been explicitly stated that they can be opened in operation.
WARNING
Electric shock due to residual charges in power components
Because of the capacitors, a hazardous voltage is present for up to 5 minutes after the power
supply has been switched o󹪜. Contact with live parts can result in death or serious injury.
Wait for 5 minutes before you check that the unit really is in a no-voltage condition and start
work.
NOTICE
Damage to equipment due to unsuitable tightening tools.
Unsuitable tightening tools or fastening methods can damage the screws of the equipment.
Only use screw inserts that exactly match the screw head.
Tighten the screws with the torque speci󹪝ed in the technical documentation.
Use a torque wrench or a mechanical precision nut runner with a dynamic torque sensor and
speed limitation system.
Adjust the tools used regularly.
NOTICE
Property damage due to loose power connections
Insu󹪟cient tightening torques or vibration can result in loose power connections. This can
result in damage due to 󹪝re, device defects or malfunctions.
Tighten all power connections to the prescribed torque.
Check all power connections at regular intervals, particularly after equipment has been
transported.
Fundamental safety instructions
1.1General safety instructions
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 15

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage

Related product manuals