WARNING
Unexpected machine movement caused by radio devices or mobile phones
Using radio devices, cellphones, or mobile WLAN devices in the immediate vicinity of the
components can result in equipment malfunction. Malfunctions may impair the functional
safety of machines and can therefore put people in danger or lead to property damage.
Therefore, if you move closer than 20cm to the components, be sure to switch o󹪜 radio
devices, cellphones or WLAN devices.
Use the "SIEMENS Industry Online Support App" or a QR code scanner only on equipment
that has already been switched o󹪜.
NOTICE
Damage to motor insulation due to excessive voltages
When operated on systems with grounded line conductors or in the event of a ground fault in
the IT system, the motor insulation can be damaged by the higher voltage against ground. If
you use motors that have insulation that is not designed for operation with grounded line
conductors, you must perform the following measures:
IT system: Use a ground fault monitor and eliminate the fault as quickly as possible.
TN or TT systems with grounded line conductor: Use an isolating transformer on the line
side.
WARNING
Fire due to inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating of components with subsequent 󹪝re
and smoke. This can cause severe injury or even death. This can also result in increased
downtime and reduced service lives for devices/systems.
Ensure compliance with the speci󹪝ed minimum clearance as ventilation clearance for the
respective component.
NOTICE
Overheating due to inadmissible mounting position
The device may overheat and therefore be damaged if mounted in an inadmissible position.
Only operate the device in admissible mounting positions.
Fundamental safety instructions
1.1General safety instructions
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 17

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage