Function description
If you use sensorless vector control with a pulling load, then the following settings are required:
Set the following parameters:
When opening the motor holding brake, enter a speed setpoint>0.
For speed setpoint = 0, and with the motor holding brake open, the load drops because the
induction motor rotates with the slip frequency as a result of the pulling load.
Set the ramp-up and ramp-down times≤10s in the ramp-function generator.
If, in quick commissioning, you have selected application class Dynamic Drive Control then
set p0502=1 (technological application: dynamic starting or reversing).
Parameter
Parameter Description Factory setting
p1610[D] Torque setpoint static (without encoder) 50%
p1750[D] Motor model con󹪝guration 0000 0000 0000
1100 bin
Advanced commissioning
8.20Motor control
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 315

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage