Parameters
Parame‐
ter
Description Factory setting
r0063 CO: Actual speed value - rpm
r0070 CO: Actual DC link voltage value - V
p0210 Device supply voltage 400V
p0212 Power unit con󹪝guration 0000 0000 bin
p0219 Braking resistor braking power 0kW
r0297 DC-link voltage overvoltage threshold - V
Further information
Interaction with other functions
When you set the braking power of the braking resistor (p0219>0), the converter disables
the Vdc_max control.
Motor and converter protection by limiting the voltage (Page344)
At the same time, p0219 de󹪝nes the regenerative power limit p1531 for vector control.
Sensorless vector control (Page310)
Advanced commissioning
8.21Electrically braking the motor
SINAMICS G120C Converters