No "Flying restart" function for group drives
It is not permissible that you enable the "Flying restart" function if the converter is
simultaneously driving several motors.
Exception: A mechanical coupling ensures that all of the motors always operate with the
same speed.
Table 8-71 Advanced settings
Parameter Description Factory setting
p0346[M] Motor excitation build-up time 0s
p0347[M] Motor de-excitation time 0s
p1201[C] BI: Flying restart enable signal source 1
p1202[D] Flying restart detection current Factory setting de‐
pendent on the
Power Module
p1203[D] Flying restart search rate factor Factory setting de‐
pendent on the
Power Module
Advanced commissioning
8.28Flying restart – switching on while the motor is running
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 347