Flow characteristic
6SHHGLQ
3RZHULQ
6SHHGSRZHU






SS
SS
SS
SS
SS
Figure8-84 Factory setting of the 󹪞ow characteristic
To set the characteristic, you require the following data from the machine manufacturer for
each speed interpolation point:
The 󹪞ow rate of the 󹪞uid-󹪞ow machine associated with the 5 selected converter speeds
At constant speed, the power drawn which is associated with the 5 󹪞ow rates corresponds to
the line frequency and mechanical throttling of the 󹪞ow rate.
Parameters
Number Name Factory setting
r0039[0...n] CO: Energy display -
p0040 Reset energy consumption display 0
r0041 Energy saved -
r0042[0...n] CO: Process energy display -
p0043 BI: Energy consumption display enabled. 0
p3320[0…n] Fluid 󹪞ow machine power, point 1 25
p3321[0…n] Fluid 󹪞ow machine speed, point 1 0
p3322[0…n] Fluid 󹪞ow machine power, point 2 50
p3323[0…n] Fluid 󹪞ow machine speed, point 2 25
p3324[0…n] Fluid 󹪞ow machine power, point 3 77
p3325[0…n] Fluid 󹪞ow machine speed, point 3 50
p3326[0…n] Fluid 󹪞ow machine power, point 4 92
p3327[0…n] Fluid 󹪞ow machine speed, point 4 75
p3328[0…n] Fluid 󹪞ow machine power, point 5 100
p3329[0…n] Fluid 󹪞ow machine speed, point 5 100
Advanced commissioning
8.33Calculating the energy saving for 󹪞uid 󹪞ow machines
SINAMICS G120C Converters
358 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage

Related product manuals