Selecting the number of drive data sets
You can use parameter p0180 to de󹪝ne the number of drive data sets (1 or 2).
Parameter Description
p0010=0 Drive commissioning: Ready
p0010=15 Drive commissioning: Data sets
p0180 Number of Drive Data Sets (DDS)
Copying the drive data sets
Parameter Description
p0819[0] Source drive data set
p0819[1] Target drive data set
p0819[2]=1 Starts the copy operation
Parameter
Parameter Description Factory setting
p0010 Drive commissioning parameter 󹪝lter 1
r0051 CO/BO: Drive data set DDS e󹪜ective -
p0180 Number of Drive Data Sets (DDS) 1
p0819[0…2] Copy drive data set DDS 0
p0820[C] BI: Drive data set DDS selection, bit 0 0
p0821[C] BI: Drive data set DDS selection, bit 1 0
p0826[M] Motor changeover, motor number 0
Advanced commissioning
8.34Switchover between di󹪜erent settings
SINAMICS G120C Converters
360 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage