Selecting the number of drive data sets
You can use parameter p0180 to dene the number of drive data sets (1 or 2).
Parameter Description
p0010=0 Drive commissioning: Ready
p0010=15 Drive commissioning: Data sets
p0180 Number of Drive Data Sets (DDS)
Copying the drive data sets
Parameter Description
p0819[0] Source drive data set
p0819[1] Target drive data set
p0819[2]=1 Starts the copy operation
Parameter
Parameter Description Factory setting
p0010 Drive commissioning parameter lter 1
r0051 CO/BO: Drive data set DDS eective -
p0180 Number of Drive Data Sets (DDS) 1
p0819[0…2] Copy drive data set DDS 0
p0820[C] BI: Drive data set DDS selection, bit 0 0
p0821[C] BI: Drive data set DDS selection, bit 1 0
p0826[M] Motor changeover, motor number 0
Advanced commissioning
8.34Switchover between dierent settings
SINAMICS G120C Converters