Number Cause Remedy
A07991 Motor data identi󹪝cation activa‐
ted
Switch on the motor and identify the motor data.
F08501 Setpoint timeout
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the monitoring time set (p2044).
F08502 Monitoring time, sign-of-life ex‐
pired
Check the PROFINET connection.
F08510 Send con󹪝guration data not valid
Check the PROFINET con󹪝guration
A08511 Receive con󹪝guration data not
valid
A08526 No cyclic connection
Activate the control with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
A08565 Consistency error a󹪜ecting adjust‐
able parameters
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
F13100 Know-how protection: Copy pro‐
tection error
The know-how protection and the copy protection for the memory card are
active. An error occurred when checking the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily o󹪜 and then on again (POWERON).
Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy pro‐
tection cannot be activated
Insert a valid memory card.
F30001 Overcurrent Check the following:
Motor data, if required, carry out commissioning
Motor connection method (Υ / Δ)
U/f operation: Assignment of rated currents of motor and Power Module
Line quality
Make sure that the line commutating reactor is connected properly
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
U/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
F30002 DC-link voltage overvoltage Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC-link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
Alarms, faults and system messages
9.5List of alarms and faults
SINAMICS G120C Converters
376 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK