5. After loading, check whether the converter outputs Alarm A01028.
– Alarm A01028:
The loaded settings are not compatible with the converter.
Delete the alarm with p0971=1.
Recommission the drive.
– No alarm A01028: Proceed with the next step.
6. Select menu "Parameter".
7. To start commissioning of the safety functions, set p10 = 95.
Corrective maintenance
10.2Downloading the converter settings
SINAMICS G120C Converters
398 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK