Control cabinet assembly
Connect the door, side panels, top and base plate of the control cabinet with the control
cabinet frame using one of the following methods:
Electrical contact surface of several cm² for each contact location
Several screw connections
Short, 󹪝nely stranded, braided copper wires with cross-sections
≥95mm²/000(3/0)(‑2)AWG
Install a shield support for shielded cables that are routed out of the control cabinet.
Connect the PE bar and the shield support to the control cabinet frame through a large
surface area to establish a good electrical connection.
Mount the control cabinet components on a bare metal mounting plate.
Connect the mounting plate to the control cabinet frame and PE bar and shield support
through a large surface area to establish a good electrical connection.
For screw connections onto painted or anodized surfaces, establish a good conductive
contact using one of the following methods:
Use special (serrated) contact washers that cut through the painted or anodized surface.
Remove the insulating coating at the contact locations.
Measures required for several control cabinets
Install equipotential bonding for all control cabinets.
Screw the frames of the control cabinets together at several locations through a large surface
area using serrated washers to establish a good electrical connection.
In plants and systems where the control cabinets are lined up next to one another, and which
are installed in two groups back to back, connect the PE bars of the two cabinet groups at as
many locations as possible.
Installing
4.2EMC-compliant setup of the machine or plant
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 41

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)