DC link components
7.2 Braking Module Booksize
176
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
Rapid discharge
Furthermore, the Braking Module can used with a braking resistor to quickly discharge the
DC link capacitors The DC link is discharged in a controlled manner via the braking resistor
once the infeed unit has been switched off and the line-up has been disconnected from the
line supply (e.g. via the main switch or line contactor). The function can be activated via a
digital input on the braking module. A quick discharge makes sense, for example, when
maintenance tasks are to be performed at the S120 Combi and/or motor installation
(reduction of the discharge time).
WARNING
Danger to life when live parts are touched after rapid discharge
After rapid discharge or if discharge is interrupted, a hazardous voltage can still remain.
Death or serious injury can result when live parts are touched.
Check that it really is in a no-voltage condition, from phase conductor to phase
conductor and phase conductor to protective conductor.
NOTICE
Material damage during fast discharge due to overvoltages
Existing voltages can damage the rapid discharge system.
Fully disconnect the drive system for rapid discharge from the line supply.
The motors must be at a standstill.
Monitoring functions
Automatic detection of braking resistors and braking power monitoring
I
2
t monitoring of the braking resistors
Temperature monitoring of the Braking Module
Short circuit and overload detection
Ground fault detection