Operation of the line connection components via a transformer 
3.8.3.1
 
Note 
If the system fault level is too low, this can result in faults at the integrated infeed of the 
SINAMICS S120 Combi Power Modules. It can also cause faults and damage to other 
equipment and devices that are conn
ected to the same line connection point as the S120 
 
Note 
Using a transformer with the S120 Combi Power Module does not replace the external line 
reactor.
 
 
Line connection conditions 
The S120 Combi is approved for operation on line supplies from S
K line
/P
n
 ≥ 70. 
If a TN line supply is specified on the secondary side, a transformer with grounded neutral 
point must be used. On the other hand, to trigger the fuse within the specified time, the loop 
resistance must be low enough.  
Any vector group with the neutral point brought out on the secondary side