9.1 Terminal Module TM54F
208
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
Note
Operational functionality of DIx+ digital inputs
For the digital inputs DIx+ to function, the reference potential must be connected to input
DIx
- in each case.
Route the ground reference of the digital inputs.
Connect the DIx input and the M1 terminal via a jumper.
9.1.3.6
X522 fail-safe digital inputs
Table 9- 6 Terminal block X522
Terminal
Designation
1)
Technical data
1
DI 4
F-DI 2 Voltage: -3 … +30 V DC
Current consumption, typical: 3.2 mA at 24 V
Electrical isolation:
Reference potential, refer to terminals 7, 8, 9, 10
All digital inputs are electrically isolated.
Level (incl. ripple)
High level: 15 … 30 V
Low level: -3 … +5 V
Input delay:
2)
for "0" → "1": 30 μs (100 Hz)
for "1" to "0": 60 μs (100 Hz)
2
DI 5+
3
DI 6
F-DI 3
4
DI 7+
5
DI 8
F-DI 4
6 DI 9+
7
DI 5-
F-DI 2
Reference potential for DI 5+
8
DI 7-
F-DI 3
Reference potential for DI 7+
9 DI 9- F-DI 4 Reference potential for DI 9+
10
M1
Reference potential for DI 4, DI 6 and DI 8
An F-DI comprises a digital input and a second digital input where, in addition, the cathode of the optocoupler is fed-out.
F-DI 2 = terminals 1, 2 and 7
F-DI 3 = terminals 3, 4 and 8
F-DI 4 = terminals 5, 6 and 9
Type: Screw terminal 1 (Page 307)
Max. connectable cross-section: 1.5 m
Tightening torque: 0.22 … 0.25 Nm
1)
DI: Digital input, F-DI: Fail-safe digital input
2)
Pure hardware delay