Additional system components 
9.1 Terminal Module TM54F 
206 
SINAMICS S120 Combi 
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5 
 
X500/X501 DRIVE-CLiQ interfaces 
Table 9- 2  X500/X501: DRIVE-CLiQ interfaces 
4  Reserved, do not use 
The blanking covers for the DRIVE
-CLiQ interfaces are included in the scope of delivery. 
Blanking covers (50 x) Article number: 6SL3066-4CA00-0AA0 
 
X514 power supply for digital outputs and sensors 
Table 9- 3  Terminals for the power supply X514 
Voltage: 24 V DC (20.4 ... 28.8 V) 
Current consumption: max. 4 A 
1)
 
Max. current via jumper in connector: 20 A (15 A ac-
cording to UL/CSA) 
Type: Screw terminal 3 (Page 307) 
Max. connectable cross-section: 2.5 mm² 
Tightening torque: 0.4 … 0.5 Nm 
M1  Electronics ground 
1)
Including the current consumption for the digital outputs and to supply the sensor
The maximum cable length that can be connected is 10 m. 
Note 
The two "+" and "M1" terminals are jumpered in the connector. This ensures that the supply 
voltage is looped through.