Additional system components
9.1 Terminal Module TM54F
206
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
9.1.3.2
X500/X501 DRIVE-CLiQ interfaces
Table 9- 2 X500/X501: DRIVE-CLiQ interfaces
Pin
Signal name
Technical data
1
TXP
Transmit data +
2
TXN
Transmit data -
3
RXP
Receive data +
4 Reserved, do not use
5
Reserved, do not use
6
RXN
Receive data -
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
Power supply
B
M (0 V)
Electronics ground
The blanking covers for the DRIVE
-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 x) Article number: 6SL3066-4CA00-0AA0
9.1.3.3
X514 power supply for digital outputs and sensors
Table 9- 3 Terminals for the power supply X514
Terminal
Designation
Technical data
+
Power supply
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: max. 4 A
1)
Max. current via jumper in connector: 20 A (15 A ac-
cording to UL/CSA)
Type: Screw terminal 3 (Page 307)
Max. connectable cross-section: 2.5 mm²
Tightening torque: 0.4 … 0.5 Nm
+
Power supply
M1
Electronics ground
M1 Electronics ground
1)
Including the current consumption for the digital outputs and to supply the sensor
The maximum cable length that can be connected is 10 m.
Note
The two "+" and "M1" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.