Encoder system connection
10.3 Sensor Module External SME20
266
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
Table 10- 16 Encoder system interface SME20
Inverse incremental signal B
4 R* Inverse reference signal R
Inverse incremental signal A
7 -Temp
1) 2)
Temperature sensor connection
3)
KTY84-1C130 / PT1000 / PTC
9 +Temp
1) 2)
Temperature sensor connection
3)
KTY84-1C130 / PT1000 / PTC
Ground, encoder power supply
Ground, encoder power supply
12 pole, article number: 6FX2003-0SA12
Measuring current via temperature sensor connection: 2 mA
Blanking cover for encoder system interface: Pöppelmann GmbH & Co. KG, Lohne,
Article number: GPN 300 F211
These connections do not have protective separation!
Accuracy of the temperature measurement:
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to DIN EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
3)
Connecting cable: Article number 6FX8002-2CA88-....