Cabinet design and EMC 
12.6 24 V DC supply 
300 
SINAMICS S120 Combi 
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5 
 
Selecting power supply units 
You are advised to use the devices in the following table. These devices meet the applicable 
requirements of EN 60204-1.  
Table 12- 5  Recommended SITOP Power 
Rated output cur-
rent [A] 
Rated input voltage [V] 
Working voltage range [V] 
Short-circuit current [A] 
5  1 / 2  AC 120 … 230 / 230 … 500 
85 … 264 / 176 … 550 
Approx. 5.5 (power up) 
Typ. 15 for 25 ms (opera-
6EP1333-3BA00-8AC0 
10  1 / 2  AC 120 … 230 / 230 … 500 
85 … 264 / 176 … 550 
Approx. 12 (power up) 
Typ. 30 for 25 ms (opera-
tion) 
6EP1334-3BA00-8AB0 
20  1 / 2  AC 120 / 230 
Approx. 23 (power up) 
Typ. 60 for 25 ms (opera-
tion) 
6EP1336-3BA00-8AA0 
3  3 AC 230 / 400 … 288 / 500 
6EP1436-3BA00-8AA0 
40  1 / 2  AC 120 / 230 
Approx. 46 (power up) 
Typ. 120 for 25 ms (opera-
tion) 
6EP1337-3BA00-8AA0 
3  3-ph. 230/400 to 288/500 
6EP1437-3BA00-8AA0 
Note 
When using an external 24 V power supply with a continuous current > 20 A, an overcurrent 
protection device must be used for the S120 Combi Power Module, the cables and the 
busbars. A circuit breaker is recommended as overcurrent protection d
evice. 
The tripping characteristic of the circuit breaker depends on the following:
 
the loads to be protected
The maximum current provided by the power supply unit in the case of a short-circuit.
Table 12- 6  Recommendation for Control Supply Module 
Rated output cur-
rent [A] 
Short-circuit current [A] 
20  3  AC 380 - 10 % (- 15 % < 1 min) 
… AC 480 + 10 %
< 24  6SL3100-1DE22-0AA1 
See also catalog NC61.