9.1 Terminal Module TM54F
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
215
9.1.3.13
X535 fail-safe digital output
Table 9- 13 Terminal block X535
Terminal
Designation
1)
Technical data
1 DI 23
F-DO 3
Voltage: -3 … +30 V DC
Current consumption, typical: 3.2 mA at 24 V
Electrical isolation: Reference potential is terminal M1.
The digital input is electrically isolated.
Level (incl. ripple)
High level: 15 … 30 V
Low level: -3 … +5 V
Input delay:
2)
for "0" → "1": 30 μs (100 Hz)
for "1" to "0": 60 μs (100 Hz)
2
DO 3+
0.5 A
Reference potential is terminal M1
0.5 A
Reference potential is terminal L1+, L2+ or L3+
Output delay:
2)
- for "0" → "1": 300 μs
for "1" → "0": 350 µs
Total current consumption of all DOs: 2 A
Max. leakage current: < 0.5 mA
Switching frequency:
for ohmic load: Max. 100 Hz
for inductive load: Max. 0.5 Hz
for lamp load: Max. 10 Hz
Maximum lamp load: 5 W
3 DO 3-
An F-DO comprises 2 digital outputs and 1 digital input for feedback signal
F-DO 3 = terminals 1, 2, and 3
Type: Screw terminal 1 (Page 307)
Max. connectable cross-section: 1.5 mm²
Tightening torque: 0.22 … 0.25 Nm
1)
DI: digital input; DO: digital output F-DO: Fail-safe digital output
2)
Pure hardware delay