Electrically connecting Motor Modules and DC link components
8.3 Connection of DC link busbars and 24 V busbars
198
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
DANGER
Danger to life due to electric shock in the event of missing touch protection
Death or serious injury can result when live parts are touched.
After removing the additional components, before recommissioning the system, y
ou
mus
t reinstall the lateral DC link cover on the S120 Combi Power Module. The DC link
lateral cover can be ordered as a spare part (order number: 6SL3161-3AP00-0AA0).
WARNING
Danger to life through electric shock due to missing DC link side covers, protective cover or
front plate
There is a danger of an electric shock through contact when the side covers, protective
cover or front plate of the DC link are missing.
Mount the supplied side covers on the first and last component in the drive line-up.
You can order missing side covers (article number: 6SL3162-5AA00-0AA0).
Close the protective cover of the connected component.
Mount the front plate on the S120 Combi.
WARNING
Danger to life due to electric shock when connecting and disconnecting 24 V connections in
operation
When opening plug connections in operation, arcs can result in severe injury or death.
Only withdraw or insert the 24 V connectors in a no-voltage state.
It is only permissible to withdraw or insert the 24 V connectors a maximum of 5 times.