Cabinet design and EMC
12.6 24 V DC supply
296
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
Note
When using cables with a cross
-section of 2.5 mm
2
, no additional protection is required on
V side if a type XLPE or EPR cable, or a cable with a similar quality and with a
thermal stability of up to 90 °C is used.
● A 24 V connector must be plugged onto the 24 V busbar between each S120 Combi,
expansion axis and DC-link component
● Insertion and withdrawal is only permissible in the no-voltage state
● Only 5 withdrawal and insertion cycles are permissible