Line-side power components 
3.4 Line supply connection via residual-current devices 
SINAMICS S120 Combi 
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5 
41 
Figure 3-2  Connecting a residual-current operated circuit breaker 
SIEMENS selectively switching AC/DC-sensitive residual current protection devices in 
accordance with EN 61009-1 of the 5SM series e.g. 5SM3646-4 or 5SM3646-4+5SW3300 
with an auxiliary disconnector (1 NC contact / 1 NO contact) for a rated current of 63 A and 
rated residual current of 0.3 A (see catalog "BETA Modular Installation Devices - ET B1"). 
-sensitive RCCBs are not suitable.