S120 Combi Power Modules 
4.2 Safety information 
SINAMICS S120 Combi 
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5 
73 
Danger to life through electric shock as well as fire hazard due to overcurrent protective 
devices that trip too late 
Overcurrent protective devices that do not trip or trip too late can cause an electric shock or 
fire. 
• To protect personnel and for fire protection purposes, at the infeed point, the short-
circuit rating and loop impedance must correspond to the specifications in the 
documentation in order for the installed overcurrent protection devices to trip within the 
specified time. 
Danger to life through interruption of the external protective conductor due to high leakage 
currents 
The drive components conduct a high leakage current via the protective conductor. 
Touching conductive parts when the protective conductor is interrupted can result in death 
or serious injury. 
• Ensure that the external protective conductor satisfies at least one of the followin
g
c
onditions: 
– It has been laid so that it is protected against mechanical damage.
1)
– I
f it is a single cable, it has a cross-section of at least 10 mm² Cu.
– If it is a conductor of a multi-conductor cable, it has a cross-section of at least 2.5
mm²
 Cu.
– It has a second protective conductor in parallel with the same cross-section.
– It complies with the local regulations for equipment with increased leakage current.
1)
Cables laid within control cabinets or closed machine housings are considered to be
adequately protected against mechanical damage. 
Danger to life through electric shock due to incorrectly laid brake cables 
If brake cables are laid without safe electrical separation, the insulation can fail with an 
electric shock. 
• Close the holding brake with the specified MOTION-CONNECT cable.
• Only use third-party cables with safe electrically separated brake cores or lay the brak
e
c
ores with safe electrical separation.