The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
192 System Manual, 12/2015, C79000-G8976-C253-04
objects: Partner and send parameters (Page 194) > "Read cycle" parameter). All setpoint
and parameter objects in the fast cycle are subjected to a 1-out-of-n check; in other words, at
the end of the fast cycle there is a check to make sure that there is a setpoint or parameter
entry for only 1 of the acquired objects.
Note
Resetting the input bits
•
If entries are made via a memory or da
ta byte, or a setpoint or parameter entry is enabled
by a memory or data bit (via the send trigger "Triggersignal"), the set entry bit or trigger
signal is automatically reset to zero by TD7onTIM.
If, however, a 1-out-of-n error is detected, the bit is not automatically reset. You then
need to reset the input bit manually or have it reset by the user program.
Image 6-17 Parameter assignment dialog of the "OpInputMonitor" system object
"Status byte for operator input" box
Status byte for operator input
The following options are available:
DB: Data block
Memory bit: Memory bit area
Output: Process output image (PIQ)
Specifies the DB number in the CPU if the data block memory area (DB) was
selected
Input box for the byte number in the selected memory area
The status byte for operator input is the output byte of the OpInputMonitor
system object.
In the status byte for operator input, the next 3 bits are assigned (explanation
see above).