290 System Manual, 06/2014, C79000-G8976-C253-03
Event ID
(hex)
Detailed
event
(hex)
Meaning
F460
Exiting state: Overflow of message buffer deactivated.
F560
051F
Buffer with messages was deleted.
F560
0520
MesA - Error in the dynamic assignment table.
F560
0521
MesA - WAN/LAN router: Error sending messages.
F560
0522
MesA could not send the acknowledgment for an org. 262 PDU to SubA.
F560
0523
MesA - WAN/LAN router; error sending over WAN/LAN driver.
F560
0524
Installation error occurred in the MesA.
F560
0530
MesA - System error occurred.
F560
0531
MesA - Error in the request for an Org4/14 message.
F560
0532
MesA - Unknown control command received.
F560
0533
MesA - Error in MesA system status list query.
F560
0534
MesA: Bad PDU detected.
Messages from clock driver
F560
0620
Installation of clock driver aborted.
F360 0621 for error code = 0: Installation of the clock driver completed
for error code = 1: Installation of clock driver aborted.
F560
0622
Entering state: Time synchronization (master) disturbed.
F460
Exiting state: Time synchronization (master) OK.
F960
0623
Entering state: Time synchronization (slave) disturbed.
F860
Exiting state: Time synchronization (slave) OK.
F560
0624
Error occurred setting the RMOS clock.
F560
0625
Error occurred reading the RMOS clock.
F360
0626
Illegal setting of the RMOS clock by
Set clock
PG service. TIM has onboard DCF77 clock.
F360
0627
Unknown message received.
F360
0628
Time synchronization PDU with incorrect ORG number received.
F360
0629
Bad synchronization PDU received from LAN.
F560
062A
Entering state: Time synchronization by DCF77 clock disturbed.
F460
Exiting state: Time synchronization by DCF77 clock OK.
F960
062B
Entering state: DCF77 clock radio signal disturbed.
F860
Exiting state: DCF77 clock radio signal OK.
F360
062C
TIM time OK. RMOS clock set for the first time.
F360
062D
Entering state: Changeover to daylight saving time.
F260
Exiting state: Changeover to standard time.
F360
062E
Entering state: Notification hour for daylight saving/standard time changeover active.
F260
Exiting state: Notification hour for daylight saving/standard time changeover completed.
F360
0630
Change in synchronization mode.
F360
0631
Daylight saving/standard time changeover performed manually.
F360
0632
Error occurred in manual daylight saving/standard time changeover.
F560 0633 Error occurred starting the synchronization task.
F560
0634
Error occurred starting the control task for synchronization.
F960 0635 Two time masters detected in one network.