User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
enter
Configure source
submenu:
Mode
parameter set as
Pt100
,
in
Low limit
parameter write
-100°C
,
in
High limit
parameter write
600°C,
for
Displaying
parameter bloc:
Format
parameter set as
numeric
,
Precision
parameter set as
0.0
,
in
Graph low
parameter write
0°C
,
in
Graph high
parameter write
100°C
,
For Relay output configuration:
touch screen and press the
Menu
button,
press the
Device configuration
button,
enter the
Built-in outputs
menu,
using the arrows in the top navigation bar, select a relay output which is connected
to heater. For this example it is the output named Out.C1 : Relay (see
Fig. 7.92
),
Mode
parameter set as
below level
, because we want the relay to switch on when
the temperature will be lower than 30°C,
Source
parameter set as
Log.ch.1:”Feedback”
, which returns Pt100 sensor
temperature,
Alarm state
parameter set as
immed. OFF
,
for
Levels
parameter block:
Level mode
parameter set as
value
,
in
Level
parameter write
30°C
,
in
Hysteresis
parameter write
5°C
, the relay will switch on below 25°C and
switch off above 35°C,
all other parameters should be on default settings,
163