EasyManua.ls Logo

Simex multicon cmc-99 - Fi2. Fi4, Ft2, Ft4 - Flowmeter Modules

Simex multicon cmc-99
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
8.5. FI2. FI4, FT2, FT4 – FLOWMETER MODULES
Fig. 8.10 Flowmeter modules
Most important parameters of F modules:
FI2 FI4 FT2 FT4
Number of inputs 2xF (flowmeters)
+ 2xI
4xF (flowmeters)
+ 4xI
2xT (tachometers)
+ 2xI
4xT (tachometers)
+ 4xI
Hardware limitations
current inputs 0mA ÷ 24mA 0mA ÷ 24mA -2mA ÷ 30mA -2mA÷ 30mA
Hardware resolution
current inputs
1µA 1µA 1µA 1µA
Precision
current inputs 0,1% @ 25˚C 0,1% @ 25˚C 0,1% @ 25˚C 0,1% @ 25˚C
Covered
MultiCon CMC-99/141
measurement ranges *
type max. type max. type max. type max.
0÷20mA
4÷20mA
0÷22mA
4÷22mA
0÷20mA
4÷20mA
0÷22mA
4÷22mA
0÷20mA
4÷20mA
0÷20mA
4÷20mA
0÷20mA
4÷20mA
0÷22mA
4÷22mA
Temperature stability 50 ppm/˚C 50 ppm/˚C 50 ppm/˚C 50 ppm/˚C
Internal impedance
current inputs type 100Ω type 100Ω type 100Ω type 100Ω
Protection
current inputs
50mA auto-reset
fuse
50mA auto-reset
fuse
50mA auto-reset
fuse
50mA auto-reset
fuse
246
FI2
2 flowmeter inputs
+ 2 current inputse
n03
n04
n05
n01
n02
GND
IN1
IN2
IN3
IN4
2 x 0-20mA
2 x 0-20mA
(flowmeters)
FI4
4 flowmeter inputs
+ 4 current inputs
n08
n09
n10
n04
n05
n06
n07
n01
n02
n03
GND
IN1
IN2
IN3
IN4
4 x 0-20mA
(flowmeters)
GND
IN5
IN6
IN7
IN8
4 x 0-20mA
FT2
2 pulse inputs
+ 2 current inputs
n07
n08
n09
n04
n05
n01
n02
n03
n04
n05
n01
n02
n03
n06
GND
IN3
IN4
2 x 0-20mA
COM2
Inp22
Inp21
COM1
Inp12
Inp11
FT4
4 pulse inputs
+ 4 current inputs
n15
n16
n17
n04
n05
n13
n14
n01
n02
n03
n04
n05
n01
n02
n03
n06
n10
n11
n07
n08
n09
n12
GND
IN5
IN6
IN7
IN8
4 x 0-20mA
COM4
Inp42
Inp41
COM3
Inp32
Inp31
COM2
Inp22
Inp21
COM1
Inp12
Inp11

Table of Contents