EasyManua.ls Logo

Simex multicon cmc-99 - Cp2, Cp4 - Optoisolated Universal Counters Modules

Simex multicon cmc-99
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
8.10. CP2, CP4 – OPTOISOLATED UNIVERSAL COUNTERS MODULES
Fig. 8.19. Optoisolated counter modules
CP2
and
CP4
are modules of universal 4-input counters (
Fig. 8.36
). Each counter has
common terminal (
COM
) and is optically isolated from other counters and
MultiCon CMC-
99/141
GND signal as well, see
Fig. 8.20
.
Most important parameters of CP2 and CP4 modules:
CP2 CP4
Number of inputs 2 groups of counter inputs
(2 groups 4 inputs, every group
optoisolated from the other signals)
4 groups of counter inputs
(4 groups 4 inputs, every group
optoisolated from the other signals)
Terminal description
Inp[n]1, Inp[n]2
- counting inputs,
pulse,
Prg[n]
- programmable inputs,
Res[n]
- reset inputs,
COM[n]
- common inputs,
[n]
=1, 2.
Inp[n]1, Inp[n]2
- counting inputs,
pulse,
Prg[n]
- programmable inputs,
Res[n]
- reset inputs,
COM[n]
- common inputs,
[n]
=1, 2, 3, 4.
Input signals voltage
levels:
logical LOW state
logical HIGH state
| Uin | < 1V
| Uin | ≥ 10V
| Uin | < 1V
| Uin | ≥ 10V
Max input voltage 30V 30V
263
CP4
4 universal counters
n08
n09
n10
n11
n12
n04
n05
n06
n07
n01
n02
n03
n20
n16
n17
n18
n19
n13
n14
n15
Prg1
Inp11
Inp12
Res1
COM1
Counter 1
Counter 2
Counter 3
Counter 4
Prg2
Inp21
Inp22
Res2
COM2
Prg3
Inp31
Inp32
Res3
COM3
Prg4
Inp41
Inp42
Res4
COM4
CP2
2 universal counters
n08
n09
n10
n04
n05
n06
n07
n01
n02
n03
Prg1
Inp11
Inp12
Res1
COM1
Counter 1
Counter 2
Prg2
Inp21
Inp22
Res2
COM2

Table of Contents