User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
TC modules parameters are:
Name
each built-in input already has a name given by the device and user cannot
change it, for description of
Name
parameter see
Fig.
7.75
.
Unit
– parameter which displays
°C
or
mV
, depending on
Mode
parameter settings,
Mode
allows to set thermocouple which is used to measurements or voltage
measurement range,
Low limit
defines measurement level bellow which in logical channel will be
displayed
Lo
state,
High limit
defines measurement level above which in logical channel will be
displayed
Hi
state,
Wire compensation
menu which allows to compensate measurement errors,
which can be caused by wrong sensor readings,
Compensation mode
allows to choose parameter, which will be used in
compensation process,
disable
– compensation is not active,
manual
– allows to compensate sensor constant offset,
Compensation
parameter which allows tu manually compensate
sensor error, written here value will be added or subtracted from
measured sensor value,
automatic
allows to compensate the difference between real temperature
and that measured by the sensor,
Actual temperature
parameter in which user enters actual
temperature near the sensor, which is measured by more reliable
thermometer,
Compensate
button which activates the compensation; value which
is written in Actual temperature parameter will be from now on used for
compensation,
Compensation
read only parameter; displays voltage value
calculated to compensate temperature measurement,
User should remember, that after changing the sensor, new settings in
Wire compensation
menu should be made.
Connectors temperature input parameters are:
Name
each built-in input already has a name given by the device and user cannot
change it, for description of Name parameter see
Fig.
7.75
.
Unit
– parameter which displays
°C
,
Mode
– parameter which displays “
Temp. of connectors
”,
Low limit
defines measurement level bellow which in logical channel will be
displayed
Lo
state,
High limit
defines measurement level above which in logical channel will be
displayed
Hi
state,
Offset
parameter which allows to add or subtract constant value to temperature
measured by connectors temperature sensor,
146