User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Next two logical channels set similarly:
Logical channel 2
:
in
Name
parameter write
Valve position
,
in
Set point
value write
1
,
Logical channel 3
:
in
Name
parameter write
Alarm state
,
in
Set point
parameter write
0
,
all other parameters should be on default settings,
Define external outputs. To do this:
touch screen and press the
Menu
button,
press the
Device configuration
button,
enter the
External outputs
menu,
using the arrows in the top navigation bar, select
Ext.out.:1
, (it is linear output),
there are three constant parameters, which are consistent
Modbus
menu
configuration:
Comm.port: MB2 (MASTER),
Device: Addr.5:”Flowmeter”,
Output channel: Out.1:HR 2h/+1,b.0-31,
for next parameters:
Source
parameter set as logical channel named as
Set point value
,
for
Input levels
block parameters:
in
Lower level
parameter write
0
,
in
Upper level
parameter write
65535
,
for
Output levels
block parameters:
in
Lower level
parameter write
0
,
in
Upper level
parameter write
65535
,
in
Alarm level
parameter write
0
,
using the arrows in the top navigation bar, select
Ext.out.:2
, (it is relay output),
there are three constant parameters, which are consistent
Modbus
menu
configuration:
Comm.port: MB2 (MASTER),
Device: Addr.5:”Flowmeter”,
Output channel: Out.2:HR 4h, b.0,
for next parameters:
Mode
parameter set as
above level
; because we want the valve to switch on
when value will be greater 0,
Source
parameter set as logical channel namer
Valve position
,
Alarm state
parameter set as
immed. OFF
, which means that when logical
channel 2 will be returning
Err
,
Hi
or
Lo
state, the output will be in low state
(valve is off),
for
Levels
block parameters:
Level
mode parameter set as
value
,
in
Level
parameter write
0
,
in
Hysteresis
parameter write
0
,
for
Timing
block parameters:
in
ON delay
parameter write
0 sec.
,
in
OFF delay
parameter write
10 sec.
,
in
Min.ON time
parameter write
10 sec.
,
172