User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Fig. 7.106. An example of the waveform
In the first step you need to configure the Profile/timer. To do this:
– touch screen and press the
Menu
button,
– press the
Device configuration
button,
– enter the
Profiles/timers
menu,
– using the arrows in the top navigation bar, select any
Profile/timer
such as
1
,
– in
Name
parameter write
Profile 1
,
–
Triggering mode
parameter set as
edge (once)
,
–
Triggering source
parameter set as
Logical channel 2
,
– in
Idle value
parameter write
0
, because we want at the beginning the Profile has 0
value on the output,
– enter the
Section list
submenu to define the sections:
•
press the green plus at the bottom left side of the screen to configure
Section num.1
:
◦ in
Duration
parameter write
5
sec.,
◦
Unit
parameter set as
second
,
◦
Shape
parameter set as
ramp
,
◦ in
Final value
parameter write
10
,
•
press the green plus at the bottom left side of the screen to configure
Section num.2
:
◦ in
Duration
parameter write
2
sec.,
◦
Unit
parameter set as
second
,
◦
Shape
parameter set as
conts.value
,
◦ in
Final value
parameter write
8
,
•
press the green plus at the bottom left side of the screen to configure
Section num.3
:
◦ in
Duration
parameter write
3
sec.,
◦
Unit
parameter set as
second
,
◦
Shape
parameter set as
ramp
,
◦ in
Final
value parameter write
4
,
•
press the green plus at the bottom left side of the screen to configure
Section num.4
:
◦ in
Duration
parameter write
1
sec.,
◦
Unit
parameter set as
second
,
◦
Shape
parameter set as
const.value
,
◦ in
Final
value parameter write
4
,
183