User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
in the
Decimal point
parameter select option: * exp (-point register) causes
that will be appear a new parameter to appear -
Decimal point register
that causes an automatic change of decimal point, depending on value of
Decimal point register
,
in the
Decimal point register
parameter set:
Register type: HOLDING
,
Register number: 3h
,
Data format: 16 bits, unsigned
,
Data shift: 0
,
Data mask: 0x0003
, because the interest to us only the first 2 bits
changing register value, the value of which determines the decimal
point, exit after the settings this menu,
-HI- state
parameter set as
if register = value
,
in the
-HI- register
parameter set:
Register type
parameter set as
HOLDING
,
in
Register number
parameter write
2h
,
Data format
parameter set as
16 bits, unsigned
,
in
Data shift
parameter write
0
,
in
Data mask
parameter write
0x0080
,
in the
-HI- value
parameter for the signal
-HI-
set the value of
0x0080
,
-LO- state
parameter set as
if register = value
,
in the
-LO- register
parameter set:
Register type
parameter set as
HOLDING
,
in
Register number
parameter write
2h
,
Data format
parameter set as
16 bits, unsigned
,
in
Data shift
parameter write
0
,
in
Data mask
parameter write
0x0040
in the
-HI- value
parameter for the signal
-HI-
set the value of
0x0040
,
-ERR- state
parameter set as
if register ≠ value
,
in the
-ERR- register
parameter set:
Register type
parameter set as
HOLDING
,
in
Register number
parameter write
2h
,
Data format
parameter set as
16 bits, unsigned
,
in
Data shift
parameter write
0
,
in
Data mask
parameter write
0x00C0
,
in the
-HI- value
parameter for the signal
-HI-
set the value of
0x0000
,
Blocks configuration mode
parameter set as
automatic
,
Max.block size
parameter set as
5
, because the slave device selected in this
example allows reading frame (using the Modbus function 03h) with up to 5
registers,
move to the
Device templates
parameter block and press
Save device template
button,
in the
Save device template
menu, enter the template name, eg
Temperature converter
(stored template can be used to configure the
device to a different address),
219