User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
◦ press the sign
'+'
and then:
◦
Output active
parameter set as
yes
,
◦
Control type
parameter set as
as a relay
,
◦ in
Output register
submenu:
– in
Register number
parameter write
8h
,
–
Data format
parameter set as
16 bits, unsigned
(this depends on
register format in Slave device),
– in
Data mask
parameter write
0x0001
,
– in
Data shift
parameter write
0
,
•
Blocks config.mode
parameter set as
manual
,
• in
Block list
submenu:
◦
Block type
parameters set as
write HOLDING reg.
,
◦
Register size
parameter set as
16-bit registers
(according to registers
format in Slave device),
◦ in
First register
parameter write
1h
,
◦ in
Last register
parameter write
2h
,
◦ create next block by pressing
'+'
sign,
◦
Block type
parameter set as
write HOLDING reg.
,
◦
Register size
parameter set as
16-bit registers
(according to registers
format in Slave device),
◦ in
First register
parameter write
4h
,
◦ in
Last register
parameter write
4h
,
◦ create next block by pressing
'+'
sign,
◦
Block type
parameters set as
write HOLDING reg.
,
◦
Register size
parameter set as
16-bit registers
(according to registers
format in Slave device),
◦ in
First register
parameter write
8h
,
◦ in
Last register
parameter write
8h
,
• move to the
Device templates
parameter block and press
Save device template
button,
◦ in the
Save device template
menu, enter the template name, eg
Write do device
(stored template can be used to configure the device to a
different address),