EasyManua.ls Logo

Simex multicon cmc-99 - Page 251

Simex multicon cmc-99
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
type
range* resolution full range full range accuracy limited range limited range accuracy
[ mV ] [ μV ] [
°C
] [
°C
] [ % ] [
°C
] [
°C
] [ % ]
K
±120 4 -200÷1370 ±8 ±0.51 -100÷1370 ±4 ±0.27
S
±30 1 -50÷1768 ±7.5 ±0.41 1768 ±6 ±0.34
J
±120 4 -210÷1200 ±6.3 ±0.44 -100÷1200 ±3 ±0.23
T
±30 1 -200÷400 ±1.9 ±0.31 -100÷400 ±1 ±0.20
N
±120 4 -200÷1300 ±12 ±0.80 -100÷1300 ±5.9 ±0.42
R
±30 1 -50÷1768 ±8.6 ±0.47 1768 ±5.5 ±0.31
E
±120 4 -200÷1000 ±4.7 ±0.40 -100÷1000 ±2.7 ±0.25
L
±120 4 -200÷800 ±4.4 ±0.44 -100÷800 ±2.5 ±0.28
B
±30 1 250÷1820 ±15 ±0,96 480÷1820 ±6 ±0,45
C
±120 4 50÷2290 ±13 ±0,51 50÷1900 ±9,2 ±0,5
* with consideration of device working in -20'C÷50'C of ambient temperature.
Tab. 8.8 Measurement accuracy for the module TC4, TC8, TC12
type norm
K
PN-EN 60584-1:2014
S
PN-EN 60584-1:2014
J
PN-EN 60584-1:2014
T
PN-EN 60584-1:2014
N
PN-EN 60584-1:2014
R
PN-EN 60584-1:2014
E
PN-EN 60584-1:2014
L
GOST R 8.595:2004
B
PN-EN 60584-1:2014
C
PN-EN 60584-1:2014
Tab. 8.9 Thermocouple norm for the module TC4, TC8, TC12
251