User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Maximal value
available for certain math functions, constant value which will be
maximal value for the function,
Averaging time
available for
Function=avarege of X
, determines logical channel
amount of samples which fits in this time and will be averaged; after this time
function enters a saturated state,
Reset now
button available for certain math functions, asynchronously resets
function value,
Reset mode
available for some math functions, depending on this parameter, the
user can set following options:
disabled
means that function after reaching maximal value, will stop on this
value,
automatic
means that function after reaching maximal value will axiomatically
resets it self and returns to initial value,
from log. channel
means that function reset is triggered from selected logical
channel,
Reset source
available for some math functions, selects a logical channel which
will be reset source for the function,
Reset triggering
available for some math functions, allows to select triggering
method from the logical channel, the user can set following options:
high level
– function resets when resetting channel is in high state,
low level
– function resets when resetting channel is in low state,
rising edge
– function resets when in resetting channel rising edge occurs,
falling edge
– function resets when in resetting channel falling edge occurs,
J input mode
– available for
Function=flip flop
, the user can set following options:
always 0
– flip flop J input is always in logical state '0',
always 1
– flip flop J input is always in logical state '1',
from log. channel
means that flip-flop J input source will be logical state
value of selected logical channel,
from channel (negation)
means that flip-flop J input source will be negated
logical state value of selected logical channel,
J input source
available for
Function=flip flop
, selects a logical channel which
will be source for flip-flop J input,
K input mode
– available for
Function=flip flop
, the user can set following options:
always 0
– flip flop K input is always in logical state '0',
always 1
– flip flop K input is always in logical state '1',
from log. channel
means that flip-flop K input source will be logical state
value of selected logical channel,
from channel (negation)
means that flip-flop K input source will be negated
logical state value of selected logical channel,
K input source
available for
Function=flip flop
, selects a logical channel which
will be source for flip-flop K input,
Clock source
available for
Function=flip flop
but unavailable if parameters
J input mode
and
K input mode
are both set as always 0, allows to select a logical
channel which will be flip-flop clock input source,
Clock triggering
available for
Function=flip flop
, the user can set following
options:
high level
flip-flop triggers when in selected in
Clock source
parameter
channel is in high logical state,
low level
flip-flop triggers when in selected in
Clock source
parameter
channel is in low logical state,
97