6-6
4007ES Panel Programmer Manual (579-1167)
Editing Standard Component Properties, Continued
Editing the IDNAC
Power Supply
To edit the Data Entry tab (Figure 6-7):
1. Configure the Depleted Battery Cutout
option. If selected, the power supply card
shuts itself off after detecting a depleted
battery condition when no AC power is
present. If this option is selected, a jumper
must be installed on the power supply (on
S527), for Canadian operation. It is
unselected by default.
2. Select the optional cards that are
connected to the power supply card. The
choices are:
• None
• City Connect
• Relay
Figure 6-7. IDNAC - Data Entry Tab
3. Click in the 25V Regulator box if a 25V regulator card, 4007-9802, is used with the FACP.
4. Click OK to confirm the selection.
To edit the AuxNAC tab
(Figure 6-8):
1. Select a point type
from the drop-down
menu.
2. Edit the AuxNAC point
type custom label. This
label should make the
point easily identifiable.
3. Click on Apply > OK
to confirm the edits.
Figure 6-8. IDNAC - AuxNAC Tab
To Edit the Aux Relay tab
(Figure 6-9):
1. Select a point type from the drop-
down menu.
2. Edit the Aux Relay point type
custom labels. This label should
make the point easily identifiable.
3. Click on Apply > OK to confirm
the edits.
Figure 6-9. IDNAC - Aux Relay Tab