EasyManua.ls Logo

Toshiba TOSVERT VF-AS3 - Page 514

Toshiba TOSVERT VF-AS3
622 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6582062
11. Table of parameters 11-12
1
9
11
F222 0222
AI4 point 1 input
value
-100 to +100 % 0 Y
[6. 6. 2]
[7. 3. 1]
F223 0223
AI4 point 1
frequency
0.0 - 590.0 Hz 0.0 Y
F224 0224
AI4 point 2 input
value
-100 to +100 % 100 Y
F225 0225
AI4 point 2
frequency
0.0 - 590.0 Hz
50.0/
60.0
*2
Y
F226 0226 AI4 point 1 rate -250 to +250 % 0 Y
[6. 6. 2]
F227 0227 AI4 point 2 rate -250 to +250 % 100 Y
F228 0228
AI5 point 1 input
value
-100 to +100 % 0 Y
[6. 6. 2]
[7. 3. 1]
F229 0229
AI5 point 1
frequency
0.0 - 590.0 Hz 0.0 Y
F230 0230
AI5 point 2 input
value
-100 to +100 % 100 Y
F231 0231
AI5 point 2
frequency
0.0 - 590.0 Hz
50.0/
60.0
*2
Y
F234 0234
Pulse train input
point 1 input value
0 - 100 % 0 Y
[6. 6. 4]
F235 0235
Pulse train input
point 1 frequency
0.0 - 590.0 Hz 0.0 Y
F236 0236
Pulse train input
point 2 input value
0 - 100 % 100 Y
F237 0237
Pulse train input
point 2 frequency
0.0 - 590.0 Hz
50.0/
60.0
*2
Y
F239 0239
Parameter for
manufacturer
------
F240 0240 Start frequency 0.0 - 10.0 Hz 0.1 Y [6. 7. 1]
F241 0241 Run frequency 0.0 - FH Hz 0.0 Y
[6. 7. 2]
F242 0242
Run frequency
hysteresis
0.0 - FH Hz 0.0 Y
F243 0243 End frequency 0.0 - 30.0 Hz 0.0 Y [6. 7. 1]
F244 0244 0 Hz dead band 0.0 - 5.0 Hz 0.0 Y [6. 7. 3]
F249 0249
DC braking carrier
frequency
1.0 - 16.0 kHz
*1
Y [6. 8. 1]
F250 0250
DC braking
frequency
0.0 - FH Hz 0.0 Y
[6. 8. 1]
[6. 8. 3]
F251 0251 DC braking current 0 - 100 % 50 Y
[6. 8. 1]
[6. 30. 4]
F252 0252 DC braking time 0.0 - 25.5 s 1.0 Y
[6. 8. 1]
[6. 8. 3]
F253 0253
Fwd/Rev DC
braking priority
0: Disabled
1: Enabled
- - 0 Y [6. 8. 1]
F254 0254
Motor shaft fixing
control
0: Disabled
1: Enabled
- - 0 Y [6. 8. 2]
F255 0255
0Hz command
select at stop
0: DC braking
1: 0 Hz command
- - 0 N [6. 8. 3]
Title
Communication
No.
Parameter name Adjustment range Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference

Table of Contents