Implementation of Modbus TCP
D301271 1013 - FGEN - multi protocol9-8
0x1141 ro active protocol
0 = EtherNet/IP™
1 = Modbus/TCP
2 = PROFINET
15 = web server
0x2400 ro System voltage U
SYS
[mV]: 0 if < 18 V
0x2401 ro Load voltage U
L
[mV]: 0 if < 18 V
0x8000 to 0x8400 ro process data inputs (32 registers per station)
0x9000 to 0x9400 rw process data outputs (32 registers per station)
0xA000 to 0xA400 ro diagnostics (32 registers per station)
0xB000 to 0xB400 rw parameters (32 registers per station)
Table 9-3:
Ident number of
the station
Address (hex.) Access
A Description