D301271 1013 - FGEN - multi protocol
6-5
FGEN-XSG16-000x
6.2 FGEN-XSG16-000x
The station is equipped with 16 channels, which can be configured individually, depending on the
specific application requirements. Up to sixteen 3 wire pnp sensors or sixteen DC actuators with a
maximum output current of 1.4 A per output can be connected.
6.2.1 Technical data
Table 6-4:
Technical data
FGEN-XSG16-
x00x
Designation FGEN-XSG16-x001
Inputs (16) 3-wire pnp-sensors
Supply (via U
B
) 18 ... 30 V DC from operating voltage
Supply current < 120 mA per connector, short-circuit protected
Switching threshold OFF/ON 2 mA / 4 mA
Low level signal voltage -3 to 5 VDC (EN 61131-2, type 1 and 3)
High level signal voltage 11 to 30 VDC (EN 61131-2, type 1 and 3)
Max. input current 6 mA
Switch-on delay 2.5 ms
Switching frequency
500 Hz
Potential isolation galvanic isolation against U
L
and Ethernet
Outputs (16) DC actuators
Output voltage 18…30 V DC from load voltage
Output current per channel 2.0 A, short-circuit proof
Load type resistive, inductive, lamp load
Simultaneity factor 0.25 for complete module,
1 × 2 A or 2 × 1 A per connector,
but only max. 9 A total current per module
Potential isolation galvanic isolation against U
B
and Ethernet
Note
General technical data for the products of the FGEN-product line can be found in chapter 3.

Table of Contents