FGEN – general technical properties
D301271 1013 - FGEN - multi protocol3-22
3.9 Status and Control Word of the FGEN-stations
The Status as well as the Control Word are mapped into the station's process data.
EtherNet/IP™
In EtherNet/IP™, the mapping can be disabled, see Gateway Class (VSC 100), GW Status register
(page 7-30) and GW Control Register (page 7-30).
Modbus TCP
→ see Register 100Ch: "Station status" (page 9-16)
PROFINET
→ see PROFINET-Error Codes (page 11-4)
3.9.1 Status Word
Meaning of the status bits
3.9.2 Control Word
The Control Word has no function at the moment, it is reserves for further use.
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Status 0
U
L
------
Diag
Warn
1 - FCE - - CFG COM U
B
-
Table 3-3:
Meaning of the
status bits
Name Meaning
DiagWarn Summarized diagnosis of the device. At least 1 channel sends diagnostics.
U
L
Load voltage not within the permissible range (18 to 30 V)
U
B
System voltage not within the permissible range (18 to 30 V)
COM I/O Communication Lost Error
No Communication on the module bus.
CFG I/O CfgModified Error
The I/O-configuration has be changed and is no longer compatible.
FCE Force Mode Active Error
The Force Mode is activated, which means, the actual output values may no match the
ones defined and sent by the field bus.