Digital outputs FGEN-OM16-x001
D301271 1013 - FGEN - multi protocol5-2
5.1 FGEN-OM16-x001
The station offers 16 digital inputs for DC actuators.
5.1.1 Technical data
5.1.2 Wiring diagrams
Ethernet
Ethernet (page 3-6)
Power supply
Operating/load voltage (page 3-6)
Input M12x1
Table 5-1:
Technical data
FGEN-OM16-
x001
Type designation FGEN-OM16-x001
Number of channels (16) DC actuators
Output voltage 18…30 V DC from load voltage
Output current per channel 2.0 A, short-circuit proof
Load type resistive, inductive, lamp load
Simultaneity factor 0.25 for complete module,
1 × 2 A or 2 × 1 A per connector,
but only max. 9 A total current per module
Potential isolation galvanic isolation against U
B
and Ethernet
Note
General technical data for the products of the FGEN-product line can be found in chapter 3.
Figure 5-1:
Wiring diagram,
output M12x1
5 PE
4 BK +
1
2 WH +
3 BU 
v