D301271 1013 - FGEN - multi protocol
7-35
VSC-Vendor Specific Classes
7.4.5 Miscellaneous Parameters Class (VSC 126)
Instance 1 / Instance 2
Diagnostic data
119
(77h)
Short circuit
output error_1
G DWORD Short-circuit at output channel
121
(79h)
Short circuit
sensor error_1
G DWORD Sensor short-circuit at channel
Parameter data
127
(7Fh)
Invert input
data_1
G/S DWORD The input signal is inverted (channel 1 to
16).
133
(85h)
Auto recovery
output_1
G/S DWORD The outputs switch on automatically after
an overload.
137
(89h)
Retriggered
recovery
output_1
G/S DWORD The outputs (channel 1 to 16) have to be
retriggered in case of an overload.
139
(8Bh)
Enable high side
output driver_1
G/S DWORD Enables the high side output driver of
channels (channel 1 to 16).
Table 7-30:
Object Instance
Attr. No.
dec.
(hex.)
Attribute name Get/
Set
Type Description
109 (6Dh)
Ethernet port
parameters
G/S DWORD 0 = Autonegotiate, AutoMDIX A
1 = 100BaseT, half duplex, linear topology
(AutoMDIX disabled)
2 = 10BaseT, full duplex, linear topology
(AutoMDIX disabled)
3 = 100BaseT, half duplex, linear topology
(AutoMDIX disabled)
4 = 10BaseT, full duplex, linear topology
(AutoMDIX disabled)
112 (70h)
IO Controller
Software revision
G DWORD The number of instances of this parameter
depends on the number of I/O controllers.
Table 7-29:
Object Instance
Attr. No.
dec.
(hex.)
Attribute name Get/
Set
Type Description