EasyManua.ls Logo

turck FGEN-AIM Series - Process Data Mapping FGEN-IM16-X001

turck FGEN-AIM Series
203 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D301271 1013 - FGEN - multi protocol
7-11
Classes and Instances of the EtherNet/IP™-stations
Process data mapping FGEN-IM16-x001
No diagnostic message,
Status- and control-word can be deactivated, see page 3-22.
Meaning of Process data bits (page 7-20)
Summarized diagnostics activated, see page 7-36
Meaning of Process data bits (page 7-20)
IN = 4 Byte
OUT = 2 Byte
IN Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Status 0
-------
Diag
Warn
1-FCE--CFGCOMU
B
-
Inputs 2 DI7
C3P2
DI6
C3P4
DI5
C0P2
DI4
C2P4
DI3
C1P2
DI2
C1P4
DI1
C0P2
DI0
C0P4
3DI15
C7P2
DI14
C7P4
DI13
C6P2
DI12
C6P4
DI11
C5P2
DI10
C5P4
DI9
C4P2
DI8
C4P4
OUT Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Control 0 Control word (MSB)
1Control word (LSB)
IN = 6 Byte
OUT = 2 Byte
IN Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Status 0
-------
Diag
Warn
1-FCE--CFGCOMU
B
-
Inputs 2 DI7
C3P2
DI6
C3P4
DI5
C0P2
DI4
C2P4
DI3
C1P2
DI2
C1P4
DI1
C0P2
DI0
C0P4
3DI15
C7P2
DI14
C7P4
DI13
C6P2
DI12
C6P4
DI11
C5P2
DI10
C5P4
DI9
C4P2
DI8
C4P4
Diagnos
tics
4 -------I/O Diag
5 --------
OUT Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Control 0 Control word (MSB)
1Control word (LSB)

Table of Contents

Related product manuals