D301271 1013 - FGEN - multi protocol
7-31
VSC-Vendor Specific Classes
7.4.3 Process Data Class (VSC102)
This class contains the process-relevant information.
Class instance
Object instance 1, standard input process data (compressed)
140
(0×8C)
Disable Protocols Get/
Set
UINT Deactivation of the used Ethernet-protocols.
Bit-assignment of the protocols:
0 = EtherNet/IP™ (can not be deactivated via
the EtherNet/IP-interface)
1 = Modbus/TCP
2 = PROFINET
3 - 14 = reserved
15 = Web-server
Note
Please refer to paragraph Class instance of the VSC, page 7-28, for the description of the class
instances for VSC.
Table 7-25:
Object instance 1,
standard input
process data
(compressed)
Attr. No.
dec. (hex.)
Attribute name Get/
Set
Type Description
100 (64h) Max object
attribute
GUSINTContains the number of the last object
attribute to be implemented.
101 (65h) Attribute list GARRAY OF
USINT
List of all attributes that are supported by
this Instance.
102 (66h) Packed process
input data
GARRAY OF
WORD
Input process data, 16-bit aligned,
compressed.
103 (67h) Process data byte
count
GUSINTThe number of bytes that are exchanged
with this Instance.
Table 7-24:
Object Instance 2,
Gateway Instance
Attr. No.
dec.
(hex.)
Attribute name Get/
Set
Type Description

Table of Contents