Implementation of Modbus TCP
D301271 1013 - FGEN - multi protocol9-14
FGEN-XSG16-x001
Meaning of the register bits (page 9-15)
register Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
packed input data
0×0000 Inputs DI7
C3P2
DI6
C3P4
DI5
C0P2
DI4
C2P4
DI3
C1P2
DI2
C1P4
DI1
C0P2
DI0
C0P4
DI15
C7P2
DI14
C7P4
DI13
C6P2
DI12
C6P4
DI11
C5P2
DI10
C5P4
DI9
C4P2
DI8
C4P4
0×0001 Status
Word
U
L
------
Diag
Warn
- FCE - - CFG COM U
B
-
0×0002 group
diagnostic
s
-------I/O Diag
--------
Inputs
0×8000 DI7
C3P2
DI6
C3P4
DI5
C0P2
DI4
C2P4
DI3
C1P2
DI2
C1P4
DI1
C0P2
DI0
C0P4
DI15
C7P2
DI14
C7P4
DI13
C6P2
DI12
C6P4
DI11
C5P2
DI10
C5P4
DI9
C4P2
DI8
C4P4
packed output data
0×0800 DO7
C3P2
DO6
C3P4
DO5
C2P2
DO4
C2P4
DO3
C1P2
DO2
C1P4
DO1
C0P2
DO0
C0P4
DO15
C7P2
DO14
C7P4
DO13
C6P2
DO12
C6P4
DO11
C5P2
DO10
C5P4
DO9
C4P2
DO8
C4P4
Outputs
0×9000 DO7
C3P2
DO6
C3P4
DO5
C2P2
DO4
C2P4
DO3
C1P2
DO2
C1P4
DO1
C0P2
DO0
C0P4
DO15
C7P2
DO14
C7P4
DO13
C6P2
DO12
C6P4
DO11
C5P2
DO10
C5P4
DO9
C4P2
DO
8
C4P4
Diagnostics
0×A000 SCS7 SCS6 SCS5 SCS4 SCS3 SCS2 SCS1 SCS0
SCO7 SCO6 SCO5 SCO4 SCO3 SCO2 SCO1 SCO0
0×A001 SCO15 SCO14 SCO13 SCO12 SCO11 SCO10 SCO9 SCO8
--------
Parameters
0×B000 --------
--------
0×B001 Inv. DI7 Inv. DI6 Inv. DI5 Inv. DI4 Inv. DI3 Inv. DI2 Inv. DI1 Inv. DI0
Inv. DI5 Inv. DI14 Inv. DI13 Inv. DI12 Inv. DI11 Inv. DI10 Inv. DI9 Inv. DI8
0×B002 SRO7 SRO6 SRO5 SRO4 SRO3 SRO2 SRO1 SRO0
SRO15 SRO14 SRO13 SRO12 SRO11 SRO10 SRO9 SRO8
0×B003 EN DO7 EN DO6 EN DO5 EN DO4 EN DO3 EN DO2 EN DO1 EN DO0
EN DO15 EN DO14 EN DO13 EN DO12 EN DO11 EN DO10 EN DO9 EN DO8