D301271 1013 - FGEN - multi protocol
7-9
Classes and Instances of the EtherNet/IP™-stations
7.3.3 Assembly Object (0×04)
Assembly Objects bind attributes of multiple objects to allow data to or from each object to be sent or
received over a single connection.
The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2, Rev. 2.1
by ODVA & ControlNet International Ltd. and adapted to FGEN.
Class attributes
Instance attributes
Common services
Configuration Assembly
Instance 106
14 byte configuration data
Byte 9, bit 1 is used to activate QuickConnect in the station (see also QuickConnect via Configuration
Assembly (page 7-5)).
Table 7-6:
Class attributes
Attr. No. Attribute name Get/
Set
Type Value
1 (0×01)
REVISION G UINT 2
2 (0×02)
MAX OBJECT INSTANCE G UINT 104
Table 7-7:
Instance
attributes
Attr. No. Attribute name Get/
Set
Type Description
3 (0×03)
DATA S ARRAY OF
BYTE
4 (0×04)
SIZE G UINT UINT Number of bytes in attr. 3
256 or variable
Table 7-8:
Common services
Service code Class Instance Service name
01 (0x01)
yes yes Get_Attribute_All
14 (0x0E)
no yes Get_Attribute_Single

Table of Contents