FGEN – general technical properties
D301271 1013 - FGEN - multi protocol3-4
3.3 General technical data
3.3.1 Technical data
Table 3-1:
Technical data
of the FGEN-
stations
Power supply
Operating voltage U
B
(VI) 18 to 30 VDC
Load voltage U
L
(VO) 18 to 30 VDC
Internal current consumption (from U
B
) < 200 mA
Connectors
Ethernet 2 x M12-female (OUT), 4-pole, D-coded
Power supply
FGEN-xxxx-5001 7/8" connector, 5-pole
FGEN-xxxx-4001 7/8" connector, 4-pole
Inputs / Outputs M12 female, 5-pole
Isolation voltages
U
BL
(U
B
against U
L
)none
U
ETH
(supply voltage against Ethernet) 500 V AC
U
ETHETH
(ETH1 against ETH 2) 500 V AC
Housing Fibre-glass reinforced Polyamide (PA6-GF30)
Size 60.4 × 220.5 × 27 mm (B × L × H)
Mounting via 4 through-holes, Ø 4.4 mm
Mounting distance
station to station
≥ 50 mm
Valid for operation in the ambient temperatures
mentioned below, with sufficient ventilation as well
as maximum load (horizontal mounting).
In case of low simultaneity factors and low ambient
temperatures, mounting distances of < 50 mm may
be possible.
Protection class IP67
Vibration test to EN 60068-2-6, IEC 68-2-47
Shock test acc. to EN 60068-2-27
EMC acc. to EN 61131-2
Temperature range
– operating 0 °C to 55 °C (32 °F to 131 °F)
– Storage and transport temperature range -25 °C to 70 °C (-13 °F to 158 °F)