EasyManua.ls Logo

turck FGEN-AIM Series - FGEN-IM16-X001; Technical Data; Wiring Diagrams

turck FGEN-AIM Series
203 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital inputs FGEN-IM16-x001
D301271 1013 - FGEN - multi protocol4-2
4.1 FGEN-IM16-x001
The station offers 16 digital inputs for 3-wire pnp sensors.
4.1.1 Technical data
4.1.2 Wiring diagrams
Ethernet
Ethernet (page 3-6)
Power supply
Operating/load voltage (page 3-6)
Input M12x1
Table 4-1:
Technical data
FGEN-IM16-
x0001
Type designation FGEN-IM16-x001
Number of channels (16) 3-wire pnp-sensors
Supply (via U
B
) 18 ... 30 VDC from operating voltage
Supply current < 120 mA per connector, short-circuit protected
Switching threshold OFF/ON 2 mA / 4 mA
Low level signal voltage -3 to 5 VDC (EN 61131-2, type 1 and 3)
High level signal voltage 11 to 30 VDC (EN 61131-2, type 1 and 3)
Max. input current 6 mA
Switch-on delay 2.5 ms
Switching frequency
500 Hz
Potential isolation galvanic isolation against U
L
and Ethernet
Note
General technical data for the products of the FGEN-product line can be found in chapter 3.
Figure 4-1:
Wiring diagram,
input M12x1
5 PE
4 BK
1 BN +
3 BU 
3 BU 
2 WH
v
C0...C7

Table of Contents

Related product manuals