Digital inputs FGEN-IM16-x001
D301271 1013 - FGEN - multi protocol4-2
4.1 FGEN-IM16-x001
The station offers 16 digital inputs for 3-wire pnp sensors.
4.1.1 Technical data
4.1.2 Wiring diagrams
Ethernet
→ Ethernet (page 3-6)
Power supply
→ Operating/load voltage (page 3-6)
Input M12x1
Table 4-1:
Technical data
FGEN-IM16-
x0001
Type designation FGEN-IM16-x001
Number of channels (16) 3-wire pnp-sensors
Supply (via U
B
) 18 ... 30 VDC from operating voltage
Supply current < 120 mA per connector, short-circuit protected
Switching threshold OFF/ON 2 mA / 4 mA
Low level signal voltage -3 to 5 VDC (EN 61131-2, type 1 and 3)
High level signal voltage 11 to 30 VDC (EN 61131-2, type 1 and 3)
Max. input current 6 mA
Switch-on delay 2.5 ms
Switching frequency
≤ 500 Hz
Potential isolation galvanic isolation against U
L
and Ethernet
Note
General technical data for the products of the FGEN-product line can be found in chapter 3.
Figure 4-1:
Wiring diagram,
input M12x1
5 PE
4 BK
1 BN +
3 BU
3 BU
2 WH
v
C0...C7