Digital in-/outputs FGEN-IOM88-x001, FGEN-XSG16-x001
D301271 1013 - FGEN - multi protocol6-2
6.1 FGEN-IOM88-x001
The station offers 8 digital inputs for 3-wire pnp sensors and 8 digital outputs for DC actuators.
6.1.1 Technical data
Table 6-1:
Technical data
FGEN-IOM88-
x001
Designation FGEN-IOM88-x001
Inputs (8) 3-wire pnp-sensors
Supply (via U
B
) 18... 30 V DC from operating voltage
Supply current < 120 mA per connector, short-circuit protected
Switching threshold OFF/ON 2 mA / 4 mA
Low level signal voltage -3 to 5 VDC (EN 61131-2, type 1 and 3)
High level signal voltage 11 to 30 VDC (EN 61131-2, type 1 and 3)
Max. input current 6 mA
Switch-on delay 2.5 ms
Switching frequency
≤ 500 Hz
Potential isolation galvanic isolation against U
L
and Ethernet
Outputs (8) DC actuators
Output voltage 18…30 V DC from load voltage
Output current per channel 2.0 A, short-circuit proof
Load type resistive, inductive, lamp load
Simultaneity factor 0.25 for complete module,
1 × 2 A or 2 × 1 A per connector,
but only max. 9 A total current per module
Potential isolation galvanic isolation against U
B
and Ethernet
Note
General technical data for the products of the FGEN-product line can be found in chapter 3.