D301271 1013 - FGEN - multi protocol
11-5
Parameters
11.4 Parameters
Two types of parameters have to be distinguished for the FGEN-stations, the PROFINET parameters of
a station and the specific parameters of the I/O-channels.
11.4.1 General module parameters - parameters for slot 0 (turck-fgen)
11.4.2
Parameters for I/O channels
Table 11-3:
Parameters for
measurement
mode
Parameter name Value Meaning
A default
setting
Outputs
behavior at commu-
nication loss
00 = set to 0 A The station switches the outputs to "0". No
error information is transmitted.
10 = keep last value The station maintains the actual output data.
Disable all diagnosis 0 = inactive A Diagnostic messages and alarms are gener-
ated.
1 = active Diagnostic messages and alarms are not
generated.
Disable output power
diagnosis
0 = inactive A The monitoring of the load voltage U
L
is acti-
vated.
1 = active An undervoltage at U
L
is not monitored.
I/O-ASSISTANT Force
Mode disable
0 = inactive A The single fieldbus protocols can be deacti-
vated.
1 = active
EtherNet/IP™
deactivate
0 = inactive A
1 = active
Modbus TCP
deactivate
0 = inactive A
1 = active
Web server
deactivate
0 = inactive A
1 = active
Table 11-4:
Parameters for
I/O channels
Parameter name Value Meaning
A default
setting
digital input x 0 = normal A
1 = inverted The input signal is inverted.