D301271 1013 - FGEN - multi protocol
11-7
Description of user data for acyclic services
11.5 Description of user data for acyclic services
The acyclic data exchange is done via Record Data CRs (CR-> Communication Relation).
Via these Record Data CRs the reading and writing of the following services is realized:
Writing of AR data
Writing of configuration data
Reading and writing of device data
Reading of diagnostic data
Reading of I/O data
Reading of Identification Data Objects (I&M functions)
11.5.1 Description of the acyclic gateway user data
Table 11-5:
Module Applica-
tion Instance
Index
(dec.)
Name Data Type r/w Comment
1 Station parameters WORD r/w Parameter data of the station (slot
0).
2 Station designation STRING r Designation of the station (slot 0).
3 Station revision STRING r Firmware revision of the station
4 Vendor-ID WORD r Ident number for TURCK
5 Station name STRING r The device name assigned to the
station.
6 Station type STRING r Device type of the station
7 Device-ID WORD r Ident number of the station
8 to 23 reserved
24 Station diagnosis WORD r Diagnostic data of the station (slot
0).
25 to 31 reserved
32 Input list Array of
BYTE
r List of all input channels in the
station
33 Output list Array of
BYTE
r List of all output channels in the
station
34 Diag. list Array of
BYTE
r List of all I/O-channel diagnostics
35
(0×23)
Parameter list Array of
BYTE
r List of all I/O-channel parameters
36 to 45039 reserved
45040
(0×AFF0)
I&M0-functions r Identification & Maintaining-
services

Table of Contents