Page 144/190 © Woodward
Cool Down
Parameter 273
Cooldown time
000s
Engine; cool down time 0 to 999 s
If the engine performs a normal shutdown (i.e. STOP mode initiated) or stoppage
by means of a class F2 alarm has been initiated, an engine cool down period with
an open GCB and frequency control is performed for this time. If the engine cool
down has terminated (cool down time has been expired) and engine speed (
Para-
meter 275) is still detected after 30 seconds, an engine failure to stop message is
displayed.
Note
An engine cool down is performed only if the reply of a closed GCB (terminal 4)
has been enabled for at least 5 seconds.